Series of MT
--------------------------------------------------------------------------------------------------

Model

MT2000T

MT3000T

MT5000T

MT6000T

MT10000T

MT15000T

MT20000T

Power

VA / W

2KVA/1.6KW

3KVA/2.4KW

5KVA/4KW

6KVA/4.8KW

10KVA/8KW

15KVA/12KW

20KVA/16KW

Input  

Voltage

220V+25%﹣23%

220V+25%﹣23% / 380V±20%

Frequency

50HZ±5%

Numbers of phases

Single phase 2 lines and earthing line

Single phase 2 lines and earthing line/3 phases 4 lines and earthing line

Power factor

0.8 (lag) ﹣1

Output

Voltage

220V±1%

Voltage stability

static ±1%

dynamic difference 2%, the loading increases from 0 to 100%

Frequency stability

50Hz±0.5%

Frequency transfer ratio

less than 1HZ/s

Dynamic response

in ±3%, 100% loading changing

Distortion

When loading <3%

Over load capacity

running for 25s in 150%

Wave crest factor

Better than 3:1

waveform

sine wave

Efficiency

AC TO  AC

81%

82%

83%

84%

84%

85%

86%

Changing time

Power network failure or recovering power supply zero failure

Inverting to bypass or from bypass to inverting full loading continuous changing

Battery

Voltage

192V

192V

192V

192V

192V

192V

192V

Capacity

12V4AH×16

12V7AH×16

12V15AH×16

12V15AH×16

12V24AH×16

12V38AH×16

12V65AH×16

Standby time

Full loading

10 minutes

8 minutes

12 minutes

10 minutes

10 minutes

15 minutes

15 minutes

Half loading

30 minutes

25 minutes

30 minutes

25 minutes

30 minutes

40 minutes

40 minutes

Battery type

Fully sealing and maintenance free lead acid battery

Charging time

After safe discharging, recovering 90% in 10 hours.

LCD display

The parameter display with back light

Self checking, status dispaly, displaying model, voltage in, voltage out, frequency, loading, working temperature and DC voltage etc.

LED display

Working status display

Working procedure status display, power supply, inverting, bypass, Output and failure display

Voice alarming

Battery discharging

Power network failure: alarming once per 4 seconds, shielding alarming is available.

Nearly using up: Once per second

UPS failure

continuous alarming

Others

Communication access

RS—232  DB9

Safety standard

EN50091﹣1/2,IEC950

Monitoring software

UPSilon2000

Noise

less than 55 db in 1 m.

Operative temperature

0℃~40℃

Relative humidity

10%-90% no coagulation

Working height

Below 5000 feet

Dimension (W×D×H)

260×495×660

260×615×675

380×790×1090

380×790×1350

Net weight (kg)

70kg / 85kg

85kg / 102kg

98kg

115kg

155kg

195kg

230kg

Remarks

MTLis MT's long time-lapse 110 hours series, external battery group, other parameters are the same as MT Series

to the capacity of MT Series 5000VA or above is external battery box.

back