| Model |
MT2000T |
MT3000T |
MT5000T |
MT6000T |
MT10000T |
MT15000T |
MT20000T |
|
Power |
VA / W |
2KVA/1.6KW |
3KVA/2.4KW |
5KVA/4KW |
6KVA/4.8KW |
10KVA/8KW |
15KVA/12KW |
20KVA/16KW |
| Input
|
Voltage |
220V+25%﹣23% |
220V+25%﹣23% / 380V±20% |
| Frequency |
50HZ±5% |
| Numbers of phases |
Single phase 2 lines and
earthing line |
Single phase 2 lines and
earthing line/3 phases 4 lines and
earthing line |
| Power
factor |
0.8 (lag) ﹣1 |
| Output
|
Voltage |
220V±1% |
| Voltage stability |
static ±1% |
| dynamic difference 2%,
the loading increases from 0 to 100% |
| Frequency stability |
50Hz±0.5% |
| Frequency transfer ratio |
less than 1HZ/s |
| Dynamic response |
in ±3%,
100% loading changing |
| Distortion |
When loading <3% |
| Over
load capacity |
running for 25s in 150% |
| Wave
crest factor |
Better than 3:1 |
| waveform |
sine wave |
|
Efficiency |
AC TO AC |
81% |
82% |
83% |
84% |
84% |
85% |
86% |
| Changing time |
Power network failure
or recovering power supply zero failure |
| Inverting to bypass or
from bypass to inverting full loading continuous changing |
| Battery
|
Voltage |
192V |
192V |
192V |
192V |
192V |
192V |
192V |
| Capacity |
12V4AH×16 |
12V7AH×16 |
12V15AH×16 |
12V15AH×16 |
12V24AH×16 |
12V38AH×16 |
12V65AH×16 |
| Standby time |
Full
loading |
10 minutes |
8 minutes |
12 minutes |
10 minutes |
10 minutes |
15 minutes |
15 minutes |
| Half
loading |
30 minutes |
25 minutes |
30 minutes |
25 minutes |
30 minutes |
40 minutes |
40 minutes |
| Battery
type |
Fully sealing and maintenance
free lead acid battery |
| Charging time |
After safe discharging,
recovering 90% in 10 hours. |
|
LCD display |
The
parameter display with back light |
Self checking, status
dispaly, displaying model, voltage in, voltage out, frequency,
loading, working temperature and DC voltage etc. |
|
LED display |
Working
status display |
Working procedure status
display, power supply, inverting, bypass, Output and failure
display |
| Voice
alarming |
Battery discharging |
Power network failure:
alarming once per 4 seconds, shielding alarming is available. |
| Nearly using up: Once
per second |
| UPS failure |
continuous alarming |
| Others
|
Communication
access |
RS—232 DB9 |
| Safety
standard |
EN50091﹣1/2,IEC950 |
| Monitoring
software |
UPSilon2000 |
| Noise |
less than 55 db in 1 m.
|
| Operative
temperature |
0℃~40℃ |
| Relative
humidity |
10%-90% no coagulation |
| Working
height |
Below 5000 feet |
| Dimension
(W×D×H) |
260×495×660 |
260×615×675 |
380×790×1090 |
380×790×1350 |
| Net
weight (kg) |
70kg / 85kg |
85kg / 102kg |
98kg |
115kg |
155kg |
195kg |
230kg |
| Remarks |
MTLis
MT's long time-lapse 1﹣10
hours series, external battery group, other parameters are the
same as MT Series |
| to
the capacity of MT Series 5000VA or above is external battery
box. |